Dual-chamber controlled air burner or Double – chamber pyrolytic burner

Types of incinerator design acceptable: Dual-chamber controlled air burner or dual – chamber pyrolytic incinerator

Products of building: The incinerator shall not have any type of asbestos, asbestos-containing compounds, mercury thermometers, and also mercury switches. Refractory materials shall be able to satisfy pertinent criteria under ISO TC33 in addition to CEN/TC 187. Waste feed system into the combustion chamber batch or continuous loading: For constant loading, the automatic charging ram or auger feed system will be capable of infusing small amounts of waste at regular intervals as well as ought to Be Able to Prevent waste from being fed when the burning chamber temperature is much less compared to 850 ° C. Additionally, the waste feed should just be able opened at or below 50 ° C in an ambient temperature level of 21 ° C.Primary combustion chamber: Shall be built with a housing (reinforced to withstand interior pressures without deflection or damage to the refractory or other elements) supported by a structural structure and supplied with refractory lining and insulation
Accessibility doors, openings, and also voids: All entry doors, openings, and also gaps shall be sealed to stop discharge of smoke in addition to exhaust gas and also to block entry of air throughout incinerator operations. Doors subjected to fire or direct warm of combustion gases shall be lined with the exact same kind and also depth of refractory mobile lining and insulation as that utilized in the burning chamber

Grate system for the primary chamber Relocating grate, traveling grate, reciprocating grate, or rotating drum grate

Main combustion chamber temperature level # 850 ° C without cool areas

Secondary combustion chamber: Shall be created with an exterior casing (strengthened to survive internal stress without deflection or damages to the refractory or various other elements ) as well as provided with refractory lining and insulation

Secondary burning chamber temperature level 1100 ° C or higher

Second burning chamber residence time # 2 minutes after the final shot of atmosphere in the second chamber